US-55812 Duluth (Minnesota) | | Projekt-ID: 1964 |
|
| |
| | |
| Teilnahme am Tag des Passivhauses: | '10 |
| Objekttyp: | Schule | Hochschule (Passivhaus Neubau) |
| Projektbeschreibung: | The Bagley Classroom is located in the Bagley Nature Area, an impressive 50 acre contiguous nature preserve within the University of Minnesota Duluth campus in the heart of downtown Duluth and near the shore of Lake Superior. The campus serves over 11,000 students. The Bagley Classroom sits on a previously developed site that offers dramatic views of the surrounding forest and pond. The existing clearing was ideal for passive and active solar, while still providing wind protection and east and west summer shading. The building serves as a multi-purpose assembly space and environmental studies center. Many departments use the facility as a field station to supplement exercises within the nature area. Engineering students use the building as a laboratory to monitor performance and learn about the construction and systems. The building incorporates many sustainable features and the project was constructed by the University of Minnesota Duluth Facilities Management Department.
|
| Bauort: | US-55812 Duluth (Minnesota) |
| Anzahl Wohn- / Nutzeinheiten: | 1 |
| Energiebezugsfläche nach PHPP: | 144 m² |
| Konstruktion: | Holzbau |
| Außenwand: | basswood paneling: 19,05mm
2x2 furring & polyisocyanurate board: 38,1mm
poly film: 8,0mm
SIP OSB Sheathing: 29,62mm
SIP EPS Core with 2x wood splices: 406,4mm
SIP OSB Sheathing: 29,62mm
felt paper: 1,6mm
air space: 6,35mm
zinc cladding U-Wert = 0,089 W/(m²K) |
| Kellerdecke / Bodenplatte: | concrete slab: 127,0mm
EPS foam: 101,6mm
poly film: 8,0mm
EPS foam: 203,2mm
U-Wert = 0,106 W/(m²K) |
| Dach: | basswood paneling: 19,05mm
2x4 furring & polyisocyanurate board: 88,9mm
poly film: 8,0mm
SIP OSB Sheathing: 29,62mm
SIP EPS Core with I-joist splices: 355,6mm
SIP OSB Sheathing: 29,62mm
EPS tapered insulation board: 76,2mm
EPDM double membrane: 6,35mm
LiveRoof Vegetative Tray System: 101,6mm U-Wert = 0,067 W/(m²K) |
| Fensterrahmen: | Trocal / Innotech, InnoNova 70.M5 uPVC
Editor's note: For a very good thermal protection and full comfort in passive buildings the calculated Uf-value 0.80 W / (m² K )according to DIN EN 10077) is recommended. The calculated Uw-value including installation and location is recommended to be <0.85 W / (m² K).
Uw-Wert = 1 W/(m²K) |
| Verglasung: | Cardinal Insulated Glass, triple (36mm):
5mm 179 LoE/argon/5mm Clear/argon/5mm 179 LoE. XLedge Stainless Steel Spacer.
g-Wert = 54 % |
| Eingangstür: | WoodMax, custom solid wood door with insulation core
Ud-Wert = 0,887 W/(m²K) |
| Lüftung: | Venmar, 700i HRV Balanced Heat Recovery Ventilation system for supply and extract air.
Merv 13 supply air filter. Merv 5 extract air filter. 170 cfm standard airflow. 450 cfm maximum airflow. Defrost HX. CO2 sensor airflow control.
Natural ventilaton and passive night cooling system utilized in the Summer. |
| Heizung: | Electric duct coil post-heater at HRV.
Electric boiler with in-floor radiant heating system. |
| Warmwasser: | Single-point tankless electric hot water heater at each handrinsing sink |
| Luftdichtheit: | n50 = 0,47/h |
| Ökologische Aspekte: | LEED Platinum Certification. Zero Energy Building (source energy) using building integrated Photovoltaic Array.
90% reduction in potable water use with composting toilets and low-flow sensor faucets. 70% reduction in artificial lighting using natural lighting and sensors. Summer natural ventilation and night cooling system. 86% FSC wood products. 17% recycled content products. 15% reused products. 35% local products. 100% low-VOC and NAUF products. Previously developed site with access to public transport. Zero increase in stormwater runoff quantity and pollutants. |
| Heizwärmebedarf: | 14 kWh/(m²a) berechnet nach PHPP |
| Gebäudeheizlast: | 21 W/(m²) berechnet nach PHPP |
| Primärenergiebedarf: | 114 kWh/(m²a) Wohn-/Nutzfläche für Heizung, Warmwasser, Hilfs- und Haushaltsstrom berechnet nach PHPP |
| Baukosten (brutto): | 5017 €/m² Energiebezugsfläche nach PHPP (Kostengruppe 200 bis 700) |
| Bauwerkskosten (brutto): | 3401 €/m² Wohn-/Nutzfläche (Kostengruppe 300+400) |
| Baujahr: | 2010 |
| Planung der Architektur: | Salmela Architect |
| Planung der Haustechnik: | Gausman & Moore |
| Planung der Bauphysik: | Carly Coulson, AIA, Passive House Designer |
| Planung der Statik: | Meyer Borgman Johnson |
| Handwerker/sonst. Beteiligte: | |
| Sonstiges: | US system:
Treated floor area: 1551 ft2
Specific heat demand: 4,56 kBTU/(ft²yr)
Heat load: 6,6 Btu/h/ft²